New Zealand · Acceptable Solution
G4/AS1: Ventilation
Acceptable Solution for natural and mechanical ventilation within the scope of clause G4.
- Edition
- Fifth edition · effective 28 July 2025
- Search coverage
- 22 of 22 PDF pages
Ventilation
Open original PDF at page 12 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
G4 VENTILATION ACCEPTABLE SOLUTION G4/AS1
Spaces within buildings
2.3.3.2 Spaces in which mechanical ventilation is used to remove or collect contaminants shall be
maintained at negative pressure relative to other spaces in the building.
COMMENT: Negative pressure reduces the likelihood of contaminants being spread to
other spaces.
2.4 Combined natural ventilation and mechanical ventilation
2.4.1 Household units and accommodation units with one external wall
2.4.1.1 This section specifies the combined natural and mechanical ventilation requirements for both
household units and accommodation units, with one external wall, such as those often found in
apartments, hotels and motels.
2.4.1.2 Habitable spaces will be naturally ventilated; and kitchens, bathrooms, toilets and laundries
will be ventilated by continuous or intermittent mechanical extract ventilation (refer to
Section 2.3).
2.4.2 Combined natural ventilation with continuous or intermittent mechanical
ventilation
2.4.2.1 Habitable spaces with one external wall and a permanent opening to a kitchen, bathroom, toilet
or laundry, within which a continuous or intermittent mechanical extract system is installed,
must be ventilated by:
a) integrating high level trickle ventilators, located within the external wall or building elements
that are integrated within the external wall (see Paragraph 2.2.2.5 for trickle ventilators); and
b) having a net openable area of windows and/ or other openings to the outside of no less than
5% of the floor area; and
c) having the kitchen, bathroom, toilet, or laundry door undercut by 20 mm; and
d) having a maximum dimension between the external wall and the furthest internal opposing
wall, when measured across the combined habitable space and the kitchen, bathroom,
toilet, or laundry, of
i) less than 10 metres for continuous mechanical extract systems, or
ii) less than 6 metres for intermittent mechanical extract systems.
COMMENT: If Paragraphs 2.4.2.1(d)(i) and (ii) both apply, then ventilation shall be
achieved by complying with Paragraph 2.4.2.1(d)(ii).
MINISTRY OF BUSINESS, INNOVATION AND EMPLOYMENT 28 JULY 2025 Page 12
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.