G4/AS1: Ventilation

Acceptable Solution for natural and mechanical ventilation within the scope of clause G4.

Ventilation
Open original PDF at page 19

Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.

G4 VENTILATION ACCEPTABLE SOLUTION G4/AS1 Ventilation options for typical apartment layouts Figure C.1.1.1A: Layout 1 Paragraph C.1.1.1 Internal wall External wall BEDROOM 6m max for Paragraph 2.2.2.2 Internal wall External wall 6m max for Paragraph 2.2.2.2 and Paragraph 2.4.2.1(d)(ii) Openable 10 m max for Paragraph 2.4.2.1(d)(i) windows and LIVING ROOM trickle ventilators in external wall OPEN BATHROOM KITCHEN Internal wall Table C.1.1.1A: Ventilation options – Layout 1 Paragraph C.1.1.1 Natural Mechanical Combined Room ventilation ventilation ventilation Bedroom Paragraph 2.2.2.2 Section 2.3 – 2.4.2.1(d)(ii) (6 m max distance) or Living room Paragraph 2.2.2.2 Section 2.3 2.4.2.1(d)(i) (10 m max distance) Paragraphs 2.4.2.1(d)(ii) (6 m max distance) or Kitchen Section 2.3 2.2.2.2 and 2.2.2.3 2.4.2.1(d)(i) (10 m max distance) 2.4.2.1(d)(ii) (6 m max distance) or Bathroom Paragraph 2.2.2.2 Section 2.3 2.4.2.1(d)(i) (10 m max distance) MINISTRY OF BUSINESS, INNOVATION AND EMPLOYMENT 28 JULY 2025 Page 19