M1/M2
Section 3: Horizontal and vertical circulation
in buildings other than dwellings
OBJECTIVE a. any reception point is located away
from the principal entrance (while still
3.1 The objective is for all people to
providing a view of it) where there is a
travel vertically and horizontally within
risk that external noise will be a problem;
buildings conveniently and without
discomfort in order to make use of all b. any reception point is easily identifiable
relevant facilities. This objective relates from the entrance doors or lobby, and
in the main, but not exclusively, to the the approach to it is direct and free from
provision of sufficient space for wheelchair obstructions;
manoeuvre and design features that make it
c. the design of the approach to any
possible for people to travel independently
reception point allows space for
within buildings.
wheelchair users to gain access to
Entrance hall and reception area the reception point;
d. the clear manoeuvring space in front
Design considerations
of any reception desk or counter is
3.2 As the entrance hall is the first point 1200mm deep and 1800mm wide if
of contact with a building’s activities and there is a knee recess at least 500mm
resources, the reception area in particular deep, or 1400mm deep and 2200mm
should not only be easily accessible but wide if there is no knee recess;
also convenient to use.
e. any reception desk or counter is designed
3.3 Where a service building has a to accommodate both standing and
reception or sales counter, there should seated visitors such that at least one
be convenient access to it and part of it section of the counter is at least 1500mm
should be at a level suitable for a wheelchair wide, with its surface no higher than
user or a seated person. Any lower section 760mm, and a knee recess, not less
should also be wheelchair-accessible on than 700mm, above floor level;
the reception side.
f. any reception point is provided with a
3.4 Designers should also be aware that hearing enhancement system, e.g. an
glazed screens in front of the reception induction loop;
point, or light sources or reflective wall
g. the floor surface is slip resistant.
surfaces, such as glazed screens, located
behind the reception point, could Internal doors
compromise the ability of a person with
Design considerations
a hearing impairment to lip read or follow
sign language. 3.7 Since doors are potential barriers,
their use should be avoided whenever
3.5 It should be possible for information
appropriate. If doors are required, the use
about the building to be easily obtained
of self-closing devices should be minimised
from a reception point or gathered from
(particularly in parts of buildings used by
notice boards and signs.
the general public) since, as described in
Note: Guidance on aids to communication
2.14, they disadvantage many people who
is available in BS 8300, and on the use of
have limited upper body strength, are
signs in the Sign design guide.
pushing prams or are carrying heavy objects.
Where closing devices are needed for fire
Provisions
control, electrically powered hold-open
3.6 An entrance hall and reception area
devices or swing-free closing devices
will satisfy Requirement M1 or M2 if:
should be used as appropriate. These are
Approved Document M Volume 2 Access to and use of buildings other than dwellings
O N L I N E V E R S I O N 29
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.