HORIZONTAL AND VERTICAL CIRCULATION IN BUILDINGS
O N L I N E V E R S I O N
M1/M2
OTHER THAN DWELLINGS
reached and where in a bank of lifts it c. the minimum dimensions of the lift cars
is located. are 1100mm wide and 1400mm deep
(see Diagram 11);
3.32 The use of visually and acoustically
reflective wall surfaces can cause d. for lifts of a size that does not allow a
discomfort for people with visual and wheelchair user to turn around within
hearing impairment. the lift car, a mirror is provided in the lift
car to enable a wheelchair user to see
3.33 Where planning allows, lift cars (used
the space behind the wheelchair;
for access between two levels only) may
be provided with opposing doors to allow a e. power-operated horizontal sliding doors
wheelchair user to leave without reversing out. provide an effective clear width of at
least 800mm (nominal);
Provisions
f. doors are fitted with timing devices and
3.34 Passenger lifts will satisfy Requirement
re-opening activators to allow adequate
M1 or M2 if:
time for people and any assistance
a. they conform to the requirements of dogs to enter or leave;
the Lift Regulations 1997, SI 1997/831
g. car controls are located between 900mm
(Note: These regulations may be met by
and 1200mm (preferably 1100mm) from
compliance with, among other things,
the car floor and at least 400mm from
the relevant British Standards, EN 81
any return wall;
series of standards, in particular BS EN
81-70:2003 Safety rules for the construction h. landing call buttons are located between
and installation of lifts. Particular 900mm and 1100mm from the floor of
applications for passenger and good the landing and at least 500mm from
passenger lifts, or, where necessary, any return wall;
by product certification issued by a i. lift landing and car doors are
Notified Body); distinguishable visually from the
b. they are accessible from the remainder adjoining walls;
of the storey;
Diagram 11 Key dimensions associated with passenger lifts
Access to and use of buildings other than dwellings Approved Document M Volume 2
34 O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.