M1
FACILITIES IN BUILDINGS OTHER THAN DWELLINGS
Provisions l. the size of wheelchair-accessible
bedrooms allows for a wheelchair user
4.24 Sleeping accommodation will satisfy
to manoeuvre at the side of a bed, then
Requirement M1 if:
transfer independently to it. An example
For all bedrooms
of a wheelchair-accessible bedroom
a. the effective clear width of the door layout is shown in Diagram 17;
from the access corridor complies
m. sanitary facilities, en-suite to a
with Table 2;
wheelchair-accessible bedroom,
b. swing doors, where provided for built-in comply with the provisions of 5.15
wardrobes and other storage systems, to 5.21 for ‘Wheelchair-accessible
open through 180°; bathrooms’ or ‘Wheelchair-accessible
shower facilities’;
c. handles on hinged and sliding doors are
easy to grip and operate and contrast n. wide angle viewers, where provided
visually with the surface of the door; in the entrance door to a wheelchair-
accessible bedroom, are located at
d. openable windows and window controls
1050mm and 1500mm above floor level,
are located between 800 and 1000mm
to enable viewing by people who are
above the floor and are easy to operate
seated or standing;
without using both hands simultaneously;
o. a balcony, where provided to a
e. all bedrooms have a visual fire alarm
wheelchair-accessible bedroom, has a
signal, in addition to the requirements
door whose effective clear width complies
of Part B;
with Table 2, has a level threshold and
f. any room numbers are indicated in has no horizontal transoms between
embossed characters; 900mm and 1200mm above the floor;
For wheelchair-accessible bedrooms p. there are no permanent obstructions
in a zone 1500mm back from any
g. at least one wheelchair-accessible
balcony doors;
bedroom is provided for every 20
bedrooms, or part thereof; q. an emergency assistance alarm
(together with a reset button) is located
h. wheelchair-accessible bedrooms are
in a wheelchair-accessible bedroom
located on accessible routes that lead
and activated by a pull cord, sited so
to all other available facilities within
that it can be operated both from the
the building;
bed and from an adjacent floor area;
i. wheelchair-accessible bedrooms
r. an emergency assistance call signal
are designed to provide a choice of
outside an accessible bedroom is located
location and have a standard of amenity
so that it can be easily seen and heard
equivalent to that of other bedrooms;
by those able to give assistance and,
j. the door from the access corridor to a
in any case, at a central control point.
wheelchair-accessible bedroom complies
Switches, outlets and controls
with the relevant provisions of ‘Internal
doors’ (see 3.10), in particular the
Design considerations
maximum permissible opening force,
Table 2 and the need for a clear space 4.25 The key factors that affect the use of
of 300mm from the leading edge of the switches, outlets and controls are ease of
door to the side wall; operation, visibility, height and freedom
from obstruction. However, there will be
k. the effective clear width of any door to
exceptions to height requirements for
an en-suite bathroom or shower room
some outlets, e.g. those set into the floor
within the wheelchair-accessible
in open plan offices.
bedroom complies with Table 2;
Approved Document M Volume 2 Access to and use of buildings other than dwellings
O N L I N E V E R S I O N 43
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.