Conservation of fuel and power: Approved Document L, Volume 2 — Buildings other than dwellings

Energy performance guidance for non-domestic buildings, covering fabric, services, controls and commissioning.

Energy & sustainability
Open original PDF at page 107

Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.

O N L I N E V E R S I O N E Appendix E: Hierarchy for establishing seasonal efficiencies of existing boilers E1 When a heating system is being replaced in an existing building, paragraph 5.4 should be followed. The seasonal efficiency of the appliance being replaced, if unknown, should be established by following the hierarchy set out below. This is based upon the Non Domestic EPC Conventions for England & Wales Issue 7.1. 1. Use Energy Technology List (ETL) product list part load values at 30% and 100% load. 2. Use current Product Characteristics Database (PCDB) values where available. 3. Use either manufacturer’s information or ‘boiler plate’ information or information from a manufacturer’s technical helpdesk. Where a gross efficiency value is established for a non- condensing boiler then a deduction of 0.05 (i.e. 5%) should be made to convert it to an appropriate seasonal efficiency. 4. Use SAP 10 tables (up to 70kW output). 5. Use suitable SBEM defaults. 97 Building Regulations 2010 Approved Document L Volume 2, 2021 edition O N L I N E V E R S I O N