Shell and core developments
2.21 If a building is offered to the market as a shell for fit-out work by the incoming occupier, the
developer should calculate a design-stage target primary energy rate, building primary energy rate,
target emission rate and building emission rate. These calculations should be submitted to the
building control body. The submission should demonstrate how the building could reasonably meet
the energy efficiency requirements after fit-out.
2.22 If some systems are not installed when a building is put on the market, reasonable assumptions
should be made in the calculation of the building primary energy rate and building emission rate
and model for the efficiencies of services that will be installed during first fit-out work. The
specification provided to the building control body should include all of the following.
a. Details of the services, including any on-site electricity generation, not provided in the base build.
b. The efficiency values assumed for these services.
c. A statement on how access to install any services, including on-site electricity generation, will
be provided during first fit-out work.
2.23 At practical completion of the base building in a shell and core development, the as-built target
primary energy rate, building primary energy rate, target emission rate and building emission rate
calculations should be based only on the building and systems as constructed; the fit-out areas
should be assumed to be conditioned to temperatures appropriate to their designated use, but no
associated energy demand included.
2.24 If an incoming occupier does first fit-out work on all or part of a building in a shell and core
development by providing or extending fixed services for any of the following:
a. heating
b. hot water
c. air-conditioning
d. mechanical ventilation
then a target primary energy rate, building primary energy rate, target emission rate and building
emission rate submission should be made to the building control body after completion to
demonstrate compliance for the part of the building covered by the fit-out work.
2.25 If fit-out work does not include providing or extending any of the fixed services for any of the
following:
a. heating
b. hot water
c. air-conditioning
d. mechanical ventilation
then any lighting systems that are installed should be at least as efficient as those assumed in the
shell developer’s initial submission.
NOTE: A new energy performance certificate is required for that part of the physical building
covered by fit-out work.
NOTE: Paragraph 9.12 outlines requirements for the building log book to be completed for shell and
core developments when first fit-out work takes place.