Conservation of fuel and power: Approved Document L, Volume 2 — Buildings other than dwellings
Energy performance guidance for non-domestic buildings, covering fabric, services, controls and commissioning.
- Edition
- 2021 edition incorporating 2023 amendments · Volume 2; later editions and transitions on source page
- Search coverage
- 116 of 116 PDF pages · 2 OCR pages
Energy & sustainability
Open original PDF at page 39 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E V E R S I O N L1(a)
Limiting the effects of solar gains in summer
4.16 In new residential buildings, as defined in Table 0.1 of Approved Document O, solar gains should be
limited in summer in accordance with the guidance in Approved Document O.
4.17 The guidance in paragraph 4.18 applies to all other buildings not covered in paragraph 4.16,
irrespective of whether they are air-conditioned.
The intention is to limit solar gains during the summer, in order to either:
a. reduce the need for air-conditioning
b. reduce the capacity of any air-conditioning system that is installed.
4.18 For each space in the building that is occupied or mechanically cooled, the solar gains through
the glazing – aggregated from April to September inclusive – should be no greater than would
occur through the relevant reference glazing systems in Table 4.3 with a defined total solar energy
transmittance (g-value) calculated according to BS EN 410. In this context, an occupied space means
a space that is intended to be occupied by the same person for a substantial part of the day. This
excludes circulation spaces and other areas of transient occupancy, such as toilets.
Table 4.3 R eference glazing systems for solar gain calculation
Type of space (as Average zone Glazing location Glazing area for Framing Glazing
defined in the height for reference reference space factor for g-value for
National Calculation space reference reference
Methodology) space space
Side-lit Any East-facing Full-width to a 10% 0.48
façade height of 1000mm
Top-lit ≤6m Roof 10% of roof area(1) 25% 0.48
>6m Roof 10% of roof area(1) 15% 0.42
NOTE:
1. ‘Roof area’ determined from the inside of the space looking out.
Limiting heat losses and gains from building services
Direct hot water and heating pipework
4.19 Hot water pipework should be insulated in all areas inside and outside the building unless it can be
demonstrated that the heat is ‘always useful’.
4.20 Insulation should be designed so that the permissible heat losses in BS 5422 for hot water services
in non-domestic buildings are not exceeded. Meeting the standards in Table 4.4 is one way of
demonstrating that this has been achieved for low temperature systems.
4.21 Insulation thickness should be calculated in accordance with BS EN ISO 12241.
NOTE: in most cases, manufacturers will be able to supply information and thicknesses for their
specific products. However, Tables 4.4 and 4.5 give indicative thicknesses for typical applications.
29
Building Regulations 2010 Approved Document L Volume 2, 2021 edition