L1(a) O N L I N E V E R S I O N Table 4.7 M aximum heat losses from domestic hot water storage vessels(1)(2) Nominal volume (litres) Heat loss (kWh/24h) Nominal volume (litres) Heat loss (kWh/24h) 200 2.1 900 4.5 300 2.6 1000 4.7 400 3.1 1100 4.8 500 3.5 1200 4.9 600 3.8 1300 5.0 700 4.1 1500 5.1 800 4.3 2000 5.2 NOTES: 1. For maximum heat losses from vessels with a storage volume less than 200 litres, see BS EN 15450. 2. The heat loss from electrically-heated cylinders (volume V litres) should not exceed either of the following. a. Point-of-use: 1.28 × (0.2 + 0.051V2/3). b. Local: 1.28 × (0.051V2/3). 32 Approved Document L Volume 2, 2021 edition Building Regulations 2010 O N L I N E V E R S I O N