L1(b), L2 O N L I N E V E R S I O N
Table 6.2 M inimum heat generator seasonal efficiency for boiler systems in existing
buildings(1)(2)
Fuel type System Boiler seasonal efficiency (gross calorific value)
Natural gas Single-boiler ≤400kW output 91%
Single-boiler 401kW–2MW output 88%
Single-boiler >2MW output 84%
Multiple-boiler 84% for any individual boiler
91% for overall multi-boiler system
LPG Single-boiler ≤2MW output 93%
Single-boiler >2MW output 88%
Multiple-boiler 88% for any individual boiler
93% for overall multi-boiler system
Oil Single-boiler 93%
Multiple-boiler 88% for any individual boiler
93% for overall multi-boiler system
NOTES:
1. Seasonal efficiencies should be calculated in line with paragraphs 6.3 to 6.6.
2. Non-condensing boilers should be fitted with a flue condensing kit where feasible and where the boiler is likely
to be able to operate in condensing mode (e.g. variable temperature circuits).
Single-boiler systems and multiple-boiler systems with identical boilers
6.3 The seasonal efficiency of the boiler should be determined using equation 6.1.
boiler seasonal efficiency = 0.81η + 0.19η equation 6.1
30% 100%
Where:
η is the gross boiler efficiency measured at 30% load
30%
η is the gross boiler efficiency measured at 100% load.
100%
NOTE: Efficiencies based on net calorific value should be converted to efficiencies based on gross
calorific value, using the appropriate conversion factor in the Standard Assessment Procedure
version 10 Table E4. Equation 6.1 assumes that the efficiency at 15% load is the same as that at 30%
load.
6.4 Equation 6.1 applies to both of the following.
a. Single-boiler systems that:
i. produce low temperature hot water
ii. have an output of less than or equal to 400kW.
b. Multiple-boiler systems that:
i. produce low temperature hot water
ii. comprise individual boilers with identical efficiencies
iii. have an output of less than or equal to 400kW.
40
Approved Document L Volume 2, 2021 edition Building Regulations 2010
O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.