Conservation of fuel and power: Approved Document L, Volume 2 — Buildings other than dwellings
Energy performance guidance for non-domestic buildings, covering fabric, services, controls and commissioning.
- Edition
- 2021 edition incorporating 2023 amendments · Volume 2; later editions and transitions on source page
- Search coverage
- 116 of 116 PDF pages · 2 OCR pages
Energy & sustainability
Open original PDF at page 55 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E V E R S I O N L1(b), L2
Table 6.5 Minimum thermal efficiencies for domestic hot water (DHW) systems
DHW system Fuel type Heat generator seasonal Product standard
type efficiency (gross calorific
value)
Direct-fired: Natural gas 91%(1) BS EN 15502-2 or
new and
LPG 92%(1) BS EN 89 or
existing
buildings BS EN 26 as appropriate
Indirect- Natural gas 91% (boiler efficiency) Use equations (as appropriate) in paragraphs 6.3 to 6.6.
fired: new
If primary return temperature ≤55°C, use equation
LPG 91% (boiler efficiency)
and existing
6.1 (0.81η + 0.19η ) to calculate boiler seasonal
buildings 30% 100%
Oil 91% (boiler efficiency) efficiency.
If primary return temperature >55°C, use boiler full
load efficiency (1.0η at 80/60°C flow/return
100%)
temperatures.
If boiler seasonal efficiency values are obtained as
net values, the factors in SAP 10 Table E4 should be
used to convert them to gross values.
Electrically- 100% assumed
heated: new
and existing
buildings
NOTE:
1. In exceptional circumstances, where a condensing boiler cannot feasibly be fitted in an existing building (for
example, where there is insufficient space for a replacement flue system), a boiler with the following minimum
seasonal efficiency may be used:
a. 80% for natural gas
b. 79% for LPG.
6.25 Where efficiency data is not readily available, efficiencies should be calculated using
manufacturers’ recovery rates and equations 6.5 and 6.6.
gross thermal efficiency = heater output / gross input equation 6.5
recovery rate specific heat
heater temperature rise
= of heater in × capacity of × equation 6.6
output of water
litres/second water
45
Building Regulations 2010 Approved Document L Volume 2, 2021 edition
O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.