England · Statutory guidance
Conservation of fuel and power: Approved Document L, Volume 1 — Dwellings
Building regulation guidance on energy efficiency and the conservation of fuel and power.
- Edition
- 2021 edition incorporating 2023 amendments · Volume 1; later editions and transitions on source page
- Search coverage
- 104 of 104 PDF pages · 3 OCR pages
Energy & sustainability
Open original PDF at page 26 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E V E R S I O N
R24-27C
2.12 When calculating the dwelling primary energy rate and dwelling emission rate for a dwelling
connected to a new district heat network, the calculation should include all heat sources to
be used up to 31 December 2027. In this way, any planned transition of the heat network to an
alternative means of heat generation will be properly accounted for. When there will be a change
in heat source up to 31 December 2027, a submission to the building control body should be made
to show both of the following.
a. That planning permission, if required, has been granted for the change.
b. That the heat network will connect to the new source, with confirmation in the form of a signed
contract to connect and supply heat.
NOTE: When calculating the dwelling primary energy rate and dwelling emission rate for a dwelling
connected to an existing district heat network the calculation should not include the effect of any
change in heat sources after the dwellings are connected.
NOTE: An existing district heat network is defined in Appendix A. A new district heat network
should be taken as meaning any other district heat network.
NOTE: New dwellings connecting to an existing district heat network should follow the standards
in Section 6.
Swimming pool basins
2.13 When calculating the dwelling primary energy rate, dwelling emission rate and dwelling fabric
energy efficiency rate for a dwelling with a swimming pool, the thermal performance of the pool
basin should not be included in the calculation. Instead, the dwelling primary energy rate, dwelling
emission rate and dwelling fabric energy efficiency rate should be calculated as if the area covered
by the pool were replaced with the equivalent area of floor with the same U-value as the pool
surround.
Party walls
2.14 When calculating the dwelling primary energy rate, dwelling emission rate and dwelling fabric
energy efficiency rate, a party wall U-value for the type of construction adopted should be applied
as set out in Table 2.1.
Table 2.1 U-values for party walls
Party wall construction U-value W/(m2·K)
Solid 0.0
Unfilled cavity with no effective edge sealing 0.5
Unfilled cavity with effective sealing around all exposed edges and in alignment with 0.2
insulation layers in abutting elements(1)
A fully filled cavity with effective sealing at all exposed edges and in alignment with 0.0
insulation layers in abutting elements(1)
NOTE:
1. It is necessary to show that the edge sealing is likely to be robust under normal site conditions.
16 Approved Document L Volume 1, 2021 edition Building Regulations 2010
O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.