England · Statutory guidance
Conservation of fuel and power: Approved Document L, Volume 1 — Dwellings
Building regulation guidance on energy efficiency and the conservation of fuel and power.
- Edition
- 2021 edition incorporating 2023 amendments · Volume 1; later editions and transitions on source page
- Search coverage
- 104 of 104 PDF pages · 3 OCR pages
Energy & sustainability
Open original PDF at page 48 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E V E R S I O N
L1(b), L2
a. Dwellings with very low heat demand (e.g. less than 10W/m2).
b. Dwelling with buffer zones for heat absorption or dissipation with high thermal mass.
5.21 It may be justified to control a heating zone rather than individual rooms in either of the
following cases.
a. In single-storey open-plan dwellings in which the living area is greater than 70% of the total
floor area. In such cases, the dwelling should be considered as a single heating zone.
b. Where two adjacent rooms have a similar function and heating requirements (e.g. kitchen and
utility room). In such cases, the adjacent rooms should be considered as a single heating zone.
NOTE: Exhaust air heat pump systems, which extract heat from the exhaust air of a dwelling, may
not need to provide independent thermostatic control to individual rooms. Providing room/
zone control on this type of system is unlikely to be economically and/or technically viable.
However, other space heating systems also in use in the same dwelling should be controlled using
thermostatic room controls as described above.
NOTE: Commissioning heating systems is covered in Section 8.
5.22 The standards in paragraphs 5.20 and 5.21 may be satisfied by providing any of the following.
a. Both of the following.
i. A thermostat in a room that the heating circuit serves.
ii. An individual thermostatic room control for each heat emitter, such as a thermostatic
radiator valve, on all heat emitters outside the room that contains the thermostat.
Thermostatic radiator valves should not be used in the same room as the thermostat.
b. An individual room/heating zone thermostat or fan coil thermostat for each room or heating
zone.
c. An individual networked heat emitter control for each emitter.
Controls in existing heating and domestic hot water systems
5.23 In addition to paragraphs 5.20 to 5.22, work on existing systems should incorporate the controls
detailed in paragraphs 5.24 to 5.27.
5.24 If domestic hot water and space heating are controlled by a single time controller in the existing
system, then these may continue to be controlled together after the work is complete. Otherwise,
domestic hot water and space heating should each have separate time controls.
5.25 If work is carried out on a system that includes a boiler, a boiler interlock should be installed.
5.26 If replacing a hot water cylinder, the replacement cylinder should have an electronic temperature
control, such as a cylinder thermostat.
5.27 If replacing a boiler, the boiler controls should meet the standards in Section 6 for the relevant wet
heating system. (The boiler controls are considered to be part of the boiler installation.)
38 Approved Document L Volume 1, 2021 edition Building Regulations 2010
O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.