England · Statutory guidance
Conservation of fuel and power: Approved Document L, Volume 1 — Dwellings
Building regulation guidance on energy efficiency and the conservation of fuel and power.
- Edition
- 2021 edition incorporating 2023 amendments · Volume 1; later editions and transitions on source page
- Search coverage
- 104 of 104 PDF pages · 3 OCR pages
Energy & sustainability
Open original PDF at page 51 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E V E R S I O N
L1(b), L2
6.3 A gas-fired range cooker with an integral central heating boiler (within a single appliance body) that
is either part of a new system or is a replacement component in an existing system should have
two independently controlled burners (one for the cooking function, and one for the boiler).
NOTE: This paragraph does not apply to appliances with fully independent boiler and cooker parts
within a shared case. In this case, the boiler should be treated as a conventional gas-fired boiler.
6.4 If a gas-fired warm air system is installed in an existing dwelling, all of the following should be met.
a. The system should be installed in accordance with BS 5864.
b. All new or replacement ductwork should be insulated in accordance with BS 5422.
c. Where controls are external to the heater, the system should be provided with a time switch/
programmer and room thermostat, or programmable room thermostat.
d. Where controls are integrated in the heater, the system should be provided with a time switch/
programmer and room temperature sensor linked to heater firing and fan speed control.
e. Independent temperature control of the hot water circuit should be implemented with a
cylinder thermostat and a timing device. When there is no demand for hot water both the pump
and circulator should switch off.
6.5 A gas-fired fixed independent space heating appliance that is installed in an existing dwelling
should meet the applicable standard(s) as follows.
a. An appliance for primary space heating should meet standards (i) to (iv) below.
i. BS EN 1266
ii. BS 7977-1
iii. BS EN 613
iv. BS EN 13278.
b. An appliance for secondary space heating should meet one or more of standards (i) to (vi) below:
i. BS EN 1266
ii. BS 7977-1
iii. BS EN 613
iv. BS EN 13278
v. BS EN 14829
vi. BS EN 449.
6.6 If a gas fire is provided as a secondary heat source as part of a combined fire and back boiler unit in
an existing system, the standards in BS 7977-2 should be met.
6.7 If a gas-fired fixed decorative fuel-effect fire is installed in an existing dwelling, both of the
following should be met.
a. The standards in BS EN 509 should be met.
b. The number of appliances should not exceed one per 100m2 of dwelling floor area.
Building Regulations 2010 Approved Document L Volume 1, 2021 edition 41
O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.