K1
Stairs and ladders
For buildings other than dwellings
1.23 Provide all of the following.
a. An unobstructed length a minimum of 1200mm on each landing.
b. Doors that do not swing across landings, except where they comply with paragraph 1.21c.
c. For access for maintenance, see paragraph 1.42.
For dwellings
1.24 A door may swing across a landing at the bottom of a flight, but only as shown in Diagram 1.8.
See para 1.24
Width of Width of
flight flight
Up
Up
At least
At least 400mm
400mm
Landing
Door
Door
Diagram 1.8 Landings next to doors in dwellings
Special stairs
Tapered treads
1.25 For the rise and going, comply with paragraphs 1.2 and 1.3. For the going of tapered treads, use the
measurements shown in Diagram 1.9.
1.26 For consecutive tapered treads, use the same going.
1.27 If a stair consists of straight and tapered treads, ensure that the going of the tapered treads is not
less than the going of the straight treads.