K4
Protection against impact with glazing
Glazing in small panes
5.6 In the context of this approved document, a ‘small pane’ is an isolated pane or one of a number of
panes held in glazing bars, traditional leaded lights or copper lights (see Diagram 5.3).
5.7 Small panes should be provided in accordance with all of the following.
a. In a small annealed glass pane, use glass with a minimum 6mm nominal thickness except in the
situation described in b.
b. In traditional leaded or copper lights, when fire resistance is not important, you may use 4mm
glass.
c. Use the dimensions and areas shown in Diagram 5.3.
See paras 5.6–5.7
max. 250mm max. 250mm
Maximum area of single pane not to exceed 0.5m²,
small panes of annealed glass should not be less
than 6mm thick
Diagram 5.3 Dimensions and areas of small panes