Protection from falling, collision and impact: Approved Document K

Guidance covering stairs, ladders, ramps, guarding and protection from collision and impact.

Stairs & circulation
Open original PDF at page 54

Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.

O N L I N E V E R S I O N K5 Safe access for cleaning windows etc. .4 Section 9: Safe access for cleaning windows etc. Safe access methods 9.1 Where a person standing on the ground, a floor or other permanent stable surface cannot safely clean a glazed surface use one of the following methods. a. Provide windows of a size and design that allows people to clean the outside safely from inside the building (see Diagram 9.1). If windows reverse for cleaning, fit a mechanism to hold the window in the reversed position. For additional guidance, see BS 8213-1. See para 9.1 (A) (B) (C) 850mm 850mm radius radius 1300mm 1300mm 610mm Not more than 1300mm Typical safe reaches for cleaning windows: (A) downwards reach through an opening light; (B) side reach through an opening light; (C) reach for cleaning an open casement with reflex hinges. DDiiaaggrraamm 99..11 SSaaffee rreeaacchheess ffoorr cclleeaanniinngg b. Provide access ladders as follows: (i) for ladders up to 6m long: as shown in Diagram 9.2 (ii) for ladders between 6m and 9m long: with safety features, as shown in Diagram 9.3. 44 Approved Documentttt KKKK,,,, 2222000011113333 eeeeddddiiiittttiiiioooonnnn Building Regulations 2010 OOO NNN LLL III NNN EEE VVV EEE RRR SSS III OOO NNN

Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.