K5
Safe access for cleaning windows etc.
.4
Section 9: Safe access for cleaning windows
etc.
Safe access methods
9.1 Where a person standing on the ground, a floor or other permanent stable surface cannot safely
clean a glazed surface use one of the following methods.
a. Provide windows of a size and design that allows people to clean the outside safely from inside
the building (see Diagram 9.1). If windows reverse for cleaning, fit a mechanism to hold the
window in the reversed position. For additional guidance, see BS 8213-1.
See para 9.1
(A) (B) (C)
850mm 850mm
radius radius
1300mm 1300mm
610mm
Not more
than 1300mm
Typical safe reaches for cleaning
windows:
(A) downwards reach through an
opening light;
(B) side reach through an opening
light;
(C) reach for cleaning an open
casement with reflex hinges.
DDiiaaggrraamm 99..11 SSaaffee rreeaacchheess ffoorr cclleeaanniinngg
b. Provide access ladders as follows:
(i) for ladders up to 6m long: as shown in Diagram 9.2
(ii) for ladders between 6m and 9m long: with safety features, as shown in Diagram 9.3.