Guidance on structural loading, foundations, walls, floors, roofs and disproportionate collapse.

Structure
Open original PDF at page 18

Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.

O N L I N E V E R S I O N A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS Diagram 3 Determination of wall thickness See para 2C5 Table 3 M inimum thickness of certain external walls, compartment walls and separating walls Height of wall Length of wall Minimum thickness of wall Not exceeding 3.5m Not exceeding 12m 190mm for whole of its height Exceeding 3.5m but not exceeding 9m Not exceeding 9m 190mm for whole of its height Exceeding 9m 290mm from the base for the height of but not exceeding 12m one storey and 190mm for the rest of its height Exceeding 9m but not exceeding 12m Not exceeding 9m 290mm from the base for the height of one storey and 190mm for the rest of its height Exceeding 9m 290mm from the base for the height of but not exceeding 12m two storeys and 190mm for the rest of its height Structure Approved Document A 16 O N L I N E V E R S I O N