England · Statutory guidance
Structure: Approved Document A
Guidance on structural loading, foundations, walls, floors, roofs and disproportionate collapse.
- Edition
- 2004 edition incorporating 2010 and 2013 amendments
- Search coverage
- 54 of 54 PDF pages · 1 OCR pages
Structure
Open original PDF at page 40 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E V E R S I O N
A1/2
Section 3: Wall cladding
General vehicle barrier, then account should be taken of
the additional imposed loading, as stipulated in
3.1 Wall cladding presents a hazard if it Approved Document K, Protection from falling,
becomes detached from the building. This collision and impact.
section provides guidance on the support
and fixing of wall cladding. An acceptable 3.6 Where the wall cladding is required to
level of safety can be achieved by different safely withstand lateral pressures from crowds,
means depending on the type and location of an appropriate design loading is given in BS EN
the cladding. The guidance given relates to 1991-1-1:2002 with its UK National Annex and
all forms of cladding, including curtain walling the Guide to Safety at Sports Grounds (4th
and glass facades. It is not intended to provide Edition, 1997).
guidance concerning the weather resistance
Fixings
of wall cladding which is included in Approved
Document C, Site preparation and resistance
3.7 The selection of fixings for supporting
to contaminants and moisture, or guidance on
cladding should be determined from a
resistance to spread of fire which is included in
consideration of the proven performance of the
Approved Document B, Fire safety, or guidance
fixing and the risks associated with the particular
in relation to sound insulation, which is included
application. In this regard applications should be
in Approved Document E, Resistance to the
designated as being either non-redundant (where
passage of sound.
the failure of a single fixing could lead to the
detachment of the cladding) or redundant (where
Technical approach
failure or excessive movement of one fixing
3.2 The cladding will meet the safety results in load sharing by adjacent fixings) and
requirement if: the required reliability of the fixing determined
accordingly.
a. the cladding is capable of safely sustaining
and transmitting to the supporting structure Note: Attention is drawn to the availability of
of the building all dead, imposed and wind anchors with an ETA gained in accordance with
loads, and the requirements of ETAG 001 Guideline for
European Technical Approval Metal Anchors
b. the cladding is securely fixed to and for use in Concrete Parts 1-5, which cover both
supported by the structure of the building. redundant and non-redundant applications, and
This shall comprise both vertical support Part 6 which covers ‘Anchors for multiple use
and horizontal restraint, and in non-structural applications’ and which can
c. provision is made, where necessary, to effectively be regarded as covering redundant
accommodate differential movement of the use. The UK definition of ‘multiple use’ is
cladding and the supporting structure of the contained in an annexe to ETAG Part 6 and is
building, and framed in such a way that all applications can be
validated as to whether or not they conform to
d. the cladding and its fixings (including this category without calculation. All ETAG parts
any support components) are of durable may be downloaded in English from www.eota.be.
materials; the design life of the fixings being
not less than that of the cladding. Fixings 3.8 The strength of fixings should be derived
shall be corrosion resistant and of a material from tests using materials representative of the
type appropriate for the local environment. material into which the fixing is to be anchored,
taking account of any inherent weaknesses that
Loading may affect the strength of the fixing, e.g. cracks
in concrete due to shrinkage and flexure, or voids
3.3 Wind loading on the cladding should be in masonry construction. The design loads will
derived from BS EN 1991-1-4:2005 with its UK generally be available from the manufacturer’s
National Annex with due consideration given to test data determined from an ETA or an extant
local increases in wind suction arising from British Standard.
funnelling of the wind through gaps between
Note: ETAs are available which cover use either
buildings.
in both cracked and non-cracked concrete or in
3.4 Where the cladding is required to support non-cracked concrete only. Those which cover
other fixtures, e.g. handrails, and fittings, e.g. both cracked and non-cracked concrete allow
antennae and signboards, account should be higher loads for use in non-cracked than in
taken of the loads and forces arising from such cracked concrete.
fixtures and fittings.
3.5 Where the wall cladding is required to
function as pedestrian guarding to stairs, ramps,
vertical drops of more than 600mm in dwellings
or more than the height of two risers (or 380mm
if not part of a stair) in other buildings, or as a
Structure Approved Document A
38 O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.