England · Statutory guidance
Structure: Approved Document A
Guidance on structural loading, foundations, walls, floors, roofs and disproportionate collapse.
- Edition
- 2004 edition incorporating 2010 and 2013 amendments
- Search coverage
- 54 of 54 PDF pages · 1 OCR pages
Structure
Open original PDF at page 42 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E V E R S I O N
A1/2
Section 4: Roof covering
Materials
4.1 All materials used to cover roofs, excluding
windows of glass in residential buildings with roof
pitches of not less than 15°, shall be capable of
safely withstanding the concentrated imposed
loads upon roofs specified in BS EN 1991-1-
1:2002 with its UK National Annex. Transparent
or translucent covering materials for roofs not
accessible except for normal maintenance and
repair are excluded from the requirement to
carry the concentrated imposed load upon roofs
if they are non-fragile or are otherwise suitably
protected against collapse.
Re-covering of roofs
4.2 The re-covering of roofs is commonly
undertaken to extend the useful life of buildings.
Roof structures may be required to carry
underdrawing or insulation provided at a time
later than their initial construction. This section
provides guidance on determining whether such
work to a roof constitutes a material alteration
under the Building Regulations.
4.3 Where the work involves a significant
change in the applied loading the structural
integrity of the roof structure and the supporting
structure should be checked to ensure that
upon completion of the work the building is not
less compliant with Requirement A1 than the
original building.
4.4 A significant change in roof loading is
when the loading upon the roof is increased by
more than 15%. Consideration might also be
given to whether the roof covering being replaced
is the original as-built covering.
4.5 Where such checking of the existing roof
structure indicates that the construction is unable
to sustain any proposed increase in loading (e.g.
due to overstressed members or unacceptable
deflection leading to ponding), appropriate
strengthening work or replacement of roofing
members should be undertaken. This is classified
as a material alteration.
4.6 In carrying out the checks mentioned in
paragraph 4.3 an increase of stress in a structural
member arising from increased loading does
not necessarily indicate that the roof structure is
less compliant than the original roof provided an
adequate factor of safety is maintained.
4.7 Where work will significantly decrease
the roof dead loading, the roof structure and its
anchorage to the supporting structure should
be checked to ensure that an adequate factor
of safety is maintained against uplift of the roof
under imposed wind loading.
Structure Approved Document A
40 O N L I N E V E R S I O N