Structure
Open original PDF at page 45 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E V E R S I O N
A3
Section 5: Reducing the sensitivity of the
building to disproportionate collapse in the
event of an accident
5.1 The requirement will be met by adopting Critical situations for design should be selected
the following approach for ensuring that the that reflect the conditions that can reasonably
building is sufficiently robust to sustain a limited be foreseen as possible during the life of the
extent of damage or failure, depending on the building. The structural form and concept and
consequence class of the building, without any protective measures should then be chosen
collapse. and the detailed design of the structure and its
elements undertaken in accordance with the
a. Determine the building’s consequence class
recommendations given in the Standards given in
from Table 11.
paragraph 5.2.
b. For Consequence Class 1 buildings –
Further guidance is given in Annexes A and
Provided the building has been designed
B to BS EN 1991-1-7:2006 Eurocode 1:
and constructed in accordance with the rules
Actions on structures – Part 1.7: General
given in this Approved Document, or other
actions – Accidental actions; with UK National
guidance referenced under Section 1, for
Annex to BS EN 1991-1-7:2006 and BS EN
meeting compliance with Requirement A1
1990:2002+A1:2005 Eurocode – Basis of
and A2 in normal use, no additional measures
structural design; with UK National Annex to
are likely to be necessary.
BS EN 1990:2002+A1:2005.
c. For Consequence Class 2a buildings –
5.2 Details of the effective horizontal and
In addition to the Consequence Class 1
vertical ties including tie force determination,
measures, provide effective horizontal ties,
together with the design approaches for
or effective anchorage of suspended floors
checking the integrity of the building following
to walls, as described in the Standards listed
the notional removal of vertical members and the
under paragraph 5.2 for framed and load-
design of key elements, are given in the following
bearing wall construction (the latter being
Standards:
defined in paragraph 5.3 below).
BS EN 1990:2002+A1:2005 Eurocode – Basis
d. For Consequence Class 2b buildings –
of structural design; with UK National Annex to
In addition to the Consequence Class 1
BS EN 1990:2002+A1:2005
measures, provide effective horizontal ties,
as described in the Standards listed under BS EN 1991-1-7:2006 Eurocode 1: Actions
paragraph 5.2 for framed and load-bearing on structures – Part 1.7: General actions –
wall construction (the latter being defined in Accidental actions; with UK National Annex to BS
paragraph 5.3 below), together with effective EN 1991-1-7: 2006 and BSI PD 6688-1-7: 2009
vertical ties, as defined in the Standards
BS EN 1992-1-1:2004 Eurocode 2: Design of
listed under paragraph 5.2, in all supporting
concrete structures – Part 1.1: General rules and
columns and walls.
rules for buildings; with UK National Annex to BS
Alternatively, check that upon the notional EN 1992-1-1:2004 and BSI PD 6687-1:2010
removal of each supporting column and each
BS EN 1993-1-1:2005 Eurocode 3: Design of
beam supporting one or more columns, or any
steel structures – Part 1.1: General rules and
nominal length of load-bearing wall (one at a
rules for buildings; with UK National Annex to BS
time in each storey of the building), the building
EN 1993-1-1:2005
remains stable and that the area of floor at any
storey at risk of collapse does not exceed 15% of BS EN 1994-1-1:2004 Eurocode 4: Design of
the floor area of that storey or 100m2, whichever composite steel and concrete structures – Part
is smaller, and does not extend further than the 1.1: General rules and rules for buildings; with UK
immediate adjacent storeys (see Diagram 24). National Annex to BS EN 1994-1-1:2004
Where the notional removal of such columns BS EN 1995-1-1:2004+A1:2008 Eurocode 5:
and lengths of walls would result in an extent of Design of timber structures – Part 1.1: General
damage in excess of the above limit, then such – Common rules and rules for buildings;
elements should be designed as a ‘key element’ with UK National Annex to BS EN 1995-1-
as defined in paragraph 5.3 below. 1:2004+A1:2008 and BSI PD 6693-1:2012
e. For Consequence Class 3 buildings – A BS EN 1996-1-1:2005+A1:2012 Eurocode 6:
systematic risk assessment of the building Design of masonry structures – Part 1.1: General
should be undertaken taking into account rules for reinforced and unreinforced masonry
all the normal hazards that may reasonably structures; with UK National Annex to
be foreseen, together with any abnormal BS EN 1996-1-1:2005+A1:2012 and BSI PD
hazards. 6697:2010
Approved Document A Structure
O N L I N E V E R S I O N 43
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.