Ventilation
Open original PDF at page 29 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E VFE1R(S2I O)N, R39, R44
Intention
In the Secretary of State’s view, requirement F1(2) and regulation 44 are met if building work that
involves installing a mechanical ventilation system, for a new or an existing building, follows the
guidance in paragraphs 4.1 to 4.3 to achieve all of the following.
a. All fixed mechanical ventilation systems for which testing and adjustment is possible are tested
and commissioned.
b. Commissioning results show that systems are operating as required to achieve adequate
ventilation, including achieving the flow rates specified in this approved document.
c. Commissioning results show that controls are operating as required to achieve adequate
ventilation.
d. The person carrying out the work gives notice to the building control body and building owner
that commissioning has been carried out following the procedure given in this document.
In the Secretary of State’s view, when building work that affects ventilation is carried out, the
requirements of regulation 39 are met if the installer provides clear and simple written guidance
for the building owner on how to operate and maintain the ventilation system, as described in
paragraphs 4.4 to 4.9.
21
Building Regulations 2010 Approved Document F Volume 2, 2021 edition
O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.