Ventilation
Open original PDF at page 35 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E V E R S I O N B
Appendix B: Performance-based ventilation
Introduction
B1 This appendix sets out the levels of moisture and other pollutants that the provisions in this
approved document are designed to control. The provisions are designed to control all of the
following.
a. Bio-effluents, as described in paragraph B2a.
b. Moisture levels, as described in paragraph B2b.
c. Indoor air pollutants, as described in paragraph B2d.
NOTE: The guidance in this approved document may not be adequate to address pollutants
from flueless combustion space heaters. This approved document does not directly address
contamination from outdoor sources.
NOTE: A strategy for achieving good indoor air quality includes reducing the release of water
vapour and air pollutants. This approved document does not provide guidance on such strategies.
Performance criteria for buildings other than dwellings
B2 The main guidance within this approved document focuses on offices. The main performance
criteria applied are as follows.
a. There should be a supply rate, in the absence of tobacco smoke or other excessive pollutants, of
10 litres per second per person. This will also satisfy the requirement of 8 litres per second per
person needed to control higher levels of bio-effluents.
b. There should be no visible mould on the inner surfaces of external walls of a properly heated
building with typical moisture generation.
c. Mould can grow whether the building is occupied or unoccupied, so the performance criteria
for surface water activity (as given in Table B2) should be met at all times, regardless of whether
there are occupants. The other pollutants listed in Table B1 are only of concern when the
building is occupied.
d. The performance criteria for indoor air pollutants are given in Table B1.
27
Building Regulations 2010 Approved Document F Volume 2, 2021 edition
O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.