Ventilation: Approved Document F, Volume 1 — Dwellings

Building regulation guidance on ventilation for dwellings and other buildings.

Ventilation
Open original PDF at page 17

Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.

O N L I N E V E R S I O N F1(1) Outside 30 litres per second NOTE: 1. The cooker hood should span at least the full width of the cooker. Diagram 1.1 M inimum kitchen extract ventilation rate in cases where a cooker hood extracts to the outside(1) 60 litres Outside per second NOTE: 1. The diagram includes a recirculating cooker hood for illustration. A recirculating cooker hood on its own does not provide a means of ventilation that complies with Part F of the Building Regulations. Diagram 1.2 M inimum ventilation rate for kitchen extract where a cooker hood does not extract to the outside(1) 9 Building Regulations 2010 Approved Document F Volume 1, 2021 edition O N L I N E V E R S I O N

Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.