England · Statutory guidance
Ventilation: Approved Document F, Volume 1 — Dwellings
Building regulation guidance on ventilation for dwellings and other buildings.
- Edition
- 2021 edition · Volume 1; later editions and transitions on source page
- Search coverage
- 62 of 62 PDF pages · 2 OCR pages
Ventilation
Open original PDF at page 19 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E V E R S I O N F1(1)
Purge ventilation
1.26 A system for purge ventilation should be provided in each habitable room.
1.27 Purge ventilation should be capable of extracting at least four air changes per hour per room
directly to the outside.
NOTE: In order to demonstrate compliance with Part O of the Building Regulations it is likely that
higher purge ventilation rates than those given in paragraph 1.29 will be required.
1.28 Purge ventilation should be delivered through one of the following means.
a. Openings (e.g. windows or doors).
b. A mechanical extract ventilation system.
1.29 Where purge ventilation is delivered through openings in a habitable room, the minimum opening
areas in Table 1.4 should be achieved. The values in Table 1.4 are based on BS 5925, which assumes
all of the following.
a. Single-sided ventilation.
b. An urban environment.
c. A wind speed of 2.1 metres per second (m/s).
d. A temperature difference of 3°C between the air inside and outside the building.
1.30 Depending on the dwelling design or the external climate, it may be possible in certain
circumstances to achieve four air changes per hour with smaller openings. If smaller openings than
those given in Table 1.4 are specified, expert advice should be sought to ensure that the design
complies with requirement F1(1).
Table 1.4 Purge ventilation openings
Opening type Minimum total area of openings
Hinged or pivot windows with an opening angle of 15 to 30 degrees 1/10 of the floor area of the room
Hinged or pivot windows with an opening angle of greater than or 1/20 of the floor area of the room
equal to 30 degrees
Opening sash windows
External doors
1.31 Hinged or pivot windows with an opening angle of less than 15 degrees are not suitable for purge
ventilation.
Performance testing
1.32 The air flow resistance of all components should be considered when specifying ventilation
systems. The complete assembly, as installed, should be designed to meet the performance
standards of this approved document. The performance of the separate components should be
measured according to the relevant parts of BS EN 13141 and other relevant standards. The relevant
test standards for common equipment types are given in Table 1.5.
11
Building Regulations 2010 Approved Document F Volume 1, 2021 edition
O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.