England · Statutory guidance
Ventilation: Approved Document F, Volume 1 — Dwellings
Building regulation guidance on ventilation for dwellings and other buildings.
- Edition
- 2021 edition · Volume 1; later editions and transitions on source page
- Search coverage
- 62 of 62 PDF pages · 2 OCR pages
Ventilation
Open original PDF at page 50 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
C O N L I N E V E R S I O N
Appendix C: Completion checklist and
commissioning sheet
C1 This installation and commissioning checklist is divided into three parts, as follows.
a. Part 1 contains the particulars of the system, installation address and installer’s details.
b. Part 2a functions as an installation checklist.
c. Part 2b is a visual inspection, or pre-commissioning, checklist.
d. Part 3 is for recording air flow measurements from fans.
Checking design air flow rates against measured air
flow rates
C2 Measured air flow rates for all fans should be recorded on Part 3: Commissioning details, as part of
the commissioning procedures given in Section 4 of this approved document.
The measured values should be compared with their respective design values to determine the
following.
a. If the measured rate for each fan is equal to or greater than the design value, then the system
meets the design standard.
b. If any measured value is lower than the design value, an adjustment should be made to correct
the system. All air flows should then be remeasured. If necessary, further adjustments should be
made until all air flows match their design values.
Demonstrating compliance
C3 All three parts of the installation and commissioning checklist should be completed.
The relevant sections of Parts 2 and 3 should be signed by a person who is both competent to install
the system and responsible for installing and commissioning the system.
C4 The three-part form should be completed for each installation address. A copy should be
submitted to the building control body as evidence that the system has been correctly installed,
inspected and commissioned.
42
Approved Document F Volume 1, 2021 edition Building Regulations 2010
O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.