Open original PDF at page 56 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
D O N L I N E V E R S I O N
Table D1 Checklist for ventilation provision in existing dwellings
Natural ventilation(1)
What is the total equivalent area of background ventilators currently in dwelling? mm2
Does each habitable room satisfy the minimum equivalent area standards in Table 1.7(2)? Yes No
Have all background ventilators been left in the open position? Yes No
Are fans and background ventilators in the same room at least 0.5m apart? Yes No
Are there working intermittent extract fans in all wet rooms? Yes No
Is there the correct number of intermittent extract fans to satisfy the standards in Table 1.1? Yes No
Does the location of fans satisfy the standards in paragraph 1.20? Yes No
Do all automatic controls have a manual override? Yes No
Does each room have a system for purge ventilation (e.g. windows)? Yes No
Do the openings in the rooms satisfy the minimum opening area standards in Table 1.4? Yes No
Do all internal doors have sufficient undercut to allow air transfer between rooms as detailed Yes No
in paragraph 1.25 (i.e. 10mm above the floor finish or 20mm above the floor surface)?
Continuous mechanical extract ventilation(1)
Does the system have a central extract fan, individual room extract fans, or both? Yes No
Does the total combined continuous rate of mechanical extract ventilation satisfy the Yes No
standards in Table 1.3?
Does each minimum mechanical extract ventilation high rate satisfy the standards in Table 1.2? Yes No
Is it certain that there are no background ventilators in wet rooms? Yes No
Do all habitable rooms have a minimum equivalent area of 5000mm2? Yes No
Does each room have a system for purge ventilation (e.g. windows)? Yes No
Do the openings in the rooms satisfy the minimum opening area standards in Table 1.4? Yes No
Do all internal doors have sufficient undercut to allow air transfer between rooms as detailed Yes No
in paragraph 1.25 (i.e. 10mm above the floor finish or 20mm above the floor surface)?
Mechanical ventilation with heat recovery(1)
Does each habitable room have mechanical supply ventilation? Yes No
Does the total continuous rate of mechanical ventilation with heat recovery satisfy the Yes No
standards in Table 1.3?
Does each minimum mechanical extract ventilation high rate satisfy the standards in Table 1.2? Yes No
Have all background ventilators been removed or sealed shut? Yes No
Does each room have a system for purge ventilation (e.g. windows)? Yes No
Do the openings in the rooms satisfy the minimum opening area standards in Table 1.4? Yes No
Do all internal doors have sufficient undercut to allow air transfer between rooms as detailed Yes No
in paragraph 1.25 (i.e. 10mm above the floor finish or 20mm above the floor surface)?
NOTES:
1. Make a visual check for mould or condensation. If either are present, install additional ventilation provisions or
seek specialist advice.
2. All references to tables and paragraphs are to Approved Document F, Volume 1: Dwellings.
48
Approved Document F Volume 1, 2021 edition Building Regulations 2010
O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.