Chapter 6: Plumbing Elements and Facilities Toilet Rooms
Grab Bars [§604.5, §609]
Grab bars are required to be mounted on the walls beside and behind the water closet.
They can be separate or continuous. When returned to walls, the length is measured to the
centerline of the return, consistent with industry practice. When attached at other points along
the bar, the length is measured to the end of the bar.
Rear Grab Bar Side Grab Bar
3366”” mmiinn 54” min
C
L 12”
42” min max
12” min 24” min
33”–36” 33”–36”
to top of to top of
gripping gripping
surface surface
The rear grab bar can be shifted to the
open side of the water closet or split
where it would conflict with the location
of flush controls required by applicable
codes (§604.5.2).
7