HORIZONTAL AND VERTICAL CIRCULATION IN BUILDINGS
O N L I N E V E R S I O N
M1/M2
OTHER THAN DWELLINGS
Corridors and passageways d. the floor is level or predominantly level
(with a gradient no steeper than 1:60),
Design considerations
with any section with a gradient of 1:20
3.11 Corridors and passageways should or steeper designed as an internal ramp
be wide enough to allow people with and in accordance with Table 1 and
buggies, people carrying cases or people Diagram 3;
on crutches to pass others on the access
e. where a section of the floor has a
route. Wheelchair users should also have
gradient, in the direction of travel,
access to adjacent rooms and spaces,
steeper than 1:60, but less steep than
be able to pass other people and, where
1:20, it rises no more than 500mm
necessary, turn through 180°. Corridors
without a level rest area at least 1500mm
narrower than indicated in this guidance,
long (with a gradient no steeper than 1:60);
or localised narrowing (e.g. at archways),
f. any sloping section extends the full
might be reasonable in some locations,
width of the corridor or, if not, the
such as in existing buildings or in some
exposed edge is clearly identified by
extensions.
visual contrast and, where necessary,
3.12 In order to help people with visual
protected by guarding;
impairment to appreciate the size of a
g. any door opening towards a corridor,
space they have entered, or to find their
which is a major access route or an
way around, there should be a visual
escape route, should be recessed so
contrast between the wall and the ceiling,
that, when fully open, it does not project
and between the wall and the floor. Such
into the corridor space, except where
attention to surface finishes should be
the doors are to minor utility facilities,
coupled with good natural and artificial
such as small store rooms and locked
lighting design.
duct cupboards;
3.13 Good acoustic design should be
h. any door from a unisex wheelchair-
employed to achieve an acoustic environment
accessible toilet projects when open
that is neither too reverberant nor too
into a corridor that is not a major
absorbent so that announcements and
access route or an escape route,
conversations can be heard clearly.
provided the corridor is at least
Provisions 1800mm wide at that point;
3.14 Corridors and passageways will i. on a major access route or an escape
satisfy Requirement M1 or M2 if: route, the wider leaf of a series of
double doors with leaves of unequal
a. elements such as columns, radiators
width is on the same side of the corridor
and fire hoses do not project into the
throughout the length of the corridor;
corridor, or where this is unavoidable, a
means of directing people around them, j. floor surface finishes with patterns that
such as a visually contrasting guard rail, could be mistaken for steps or changes
is provided; of level are avoided;
b. they have an unobstructed width k. floor finishes are slip resistant;
(excluding any projections into the space)
l. any glazed screens alongside a corridor
along their length of at least 1200mm;
are clearly defined with manifestation
c. where they have an unobstructed width on the glass that complies with Approved
of less than 1800mm, they have passing Document K, section 7.
places at least 1800mm long and with
an unobstructed width of at least 1800mm
at reasonable intervals, e.g. at corridor
junctions, to allow wheelchair users to
pass each other;
Approved Document M Volume 2 Access to and use of buildings other than dwellings