HORIZONTAL AND VERTICAL CIRCULATION IN BUILDINGS
O N L I N E V E R S I O N
M1/M2
OTHER THAN DWELLINGS
Note: In respect of 3.14(b), for school 3.18 Signs indicating the location of
buildings, the preferred corridor width a lifting device accessible by mobility-
dimension is 2700mm where there are impaired people should be clearly visible
lockers within the corridor. from the building entrance. Additionally, a
sign identifying the floor reached should be
Internal lobbies
provided on each landing in a location that
Design considerations can be easily seen from the lifting device
and is designed so that it contrasts visually
3.15 An internal lobby should allow a
with its surrounding.
wheelchair user, with or without a companion,
or a person pushing a pram or buggy to 3.19 Whatever lifting device is chosen,
move clear of one door before attempting internal stairs should always be provided
to open the second door, as indicated in as an alternative means of vertical access,
2.27, under ‘External lobbies’. and designed to suit ambulant disabled
people and those with impaired sight.
Provisions
3.20 A ramp may also be provided on an
3.16 Internal lobbies will satisfy internal circulation route to a suitable lifting
Requirement M1 or M2 if: device, if a change of level is unavoidable.
a. their length with single swing doors is
Provision of lifting devices
in accordance with Diagram 10;
Design considerations
b. their length with double swing doors is
at least (DP1 + DP2 + 1570mm); 3.21 For all buildings, a passenger lift
is the most suitable form of access for
c. their width (excluding any projections
people moving from one storey to another.
into the space) is at least 1200mm (or
(DL1 or DL2) + 300mm) whichever is the 3.22 For existing buildings, and in
greater when single leaf doors are used, exceptional circumstances for new
and at least 1800mm when double leaf developments with particular constraints
doors are used; (e.g. a listed building or an infill site in a
historic town centre), where a passenger
d. glazing within the lobby does not create
lift cannot be accommodated, a vertical
distracting reflections;
lifting platform (platform lift), although not
e. any junctions of floor surface materials equivalent to a passenger lift, may be
at the entrance to the lobby area do not considered as an alternative option to
create a potential trip hazard; provide access for persons with impaired
f. any columns, ducts and similar full mobility.
height elements that project into the 3.23 In exceptional circumstances in an
lobby by more than 100mm are protected existing building, a wheelchair platform
by a visually contrasting guard rail. stairlift may be considered, provided
its installation does not conflict with
Vertical circulation within
requirements for means of escape.
the building
Provisions
Design considerations
3.24 The provision of lifting devices will
3.17 A passenger lift is the most suitable
satisfy Requirement M1 or M2 if:
means of vertical access and should be
provided wherever possible. However, a. new developments have a passenger lift
given the space constraints in some serving all storeys;
buildings, it may not always be possible
to install the type and size of passenger lift
that would be suitable for use by all, and
other options may need to be considered
to provide for users with mobility impairments.
Access to and use of buildings other than dwellings Approved Document M Volume 2