M1/M3
Section 5: Sanitary accommodation in
buildings other than dwellings
OBJECTIVES Provisions
5.1 In principle, suitable sanitary 5.4 Sanitary accommodation will satisfy
accommodation should be available to Requirement M1 or M3 if:
everybody, including sanitary accommodation
a. any bath or washbasin tap is either
designed for wheelchair users, ambulant
controlled automatically, or is capable
disabled people, people of either sex
of being operated using a closed fist,
with babies and small children or people
e.g. by lever action;
encumbered by luggage.
b. terminal fittings comply with Guidance
Note: Where ambulant sanitary
Note G18.5 of the Guidance Document
accommodation is being provided,
relating to Schedule 2: Requirements
Approved Document T provides additional
for Water Fittings, of the Water Supply
guidance on the design considerations of
(Water Fittings) Regulations 1999,
ambulant single-sex toilets and ambulant
SI 1999/1148;
universal toilet accommodation to meet
c. door handles and other ironmongery
requirement T1.
comply with provisions 3.10 (d) and (e)
5.2 In multi-storey buildings, the consistent
of ‘Internal doors’;
location of toilets on each floor can help
d. WC compartment doors, and doors to
people with learning difficulties to locate
wheelchair-accessible unisex toilets,
these facilities easily.
changing rooms or shower rooms are
Sanitary accommodation generally fitted with light action privacy bolts so
that they can be operated by people with
Design considerations
limited dexterity and, if required to self-
5.3 A number of issues need to be close, can be opened using a force at
considered in connection with all forms of the leading edge of not more than 30N
sanitary accommodation. These relate to from 0° (the door in the closed position)
the needs of people with visual or hearing to 30° open, and not more than 22.5N
impairments, people with learning difficulties from 30° to 60° of the opening cycle;
and people whose lack of tactile sensitivity
e. WC compartment doors, and doors
can cause them to be injured by touching
to wheelchair-accessible unisex toilets,
hot surfaces. Taps and WC cubicle doors
changing rooms or shower rooms have
should be operable by people with limited
an emergency release mechanism so
strength or manual dexterity and doors
that they are capable of being opened
to cubicles should be capable of being
outwards, from the outside, in case of
opened if a person has collapsed against
emergency;
them while inside the cubicle. Preferably,
all doors to WC cubicles and wheelchair- f. doors, when open, do not obstruct
accessible unisex toilets open out or, if emergency escape routes;
they open in, the door swing should not
g. any fire alarm emits a visual and audible
encroach into the wheelchair turning space
signal to warn occupants with hearing
or minimum activity space. Where possible,
or visual impairments;
light switches with large push pads should
be used in preference to pull cords (see 4.28).
Approved Document M Volume 2 Access to and use of buildings other than dwellings
O N L I N E V E R S I O N 47