Conservation of fuel and power: Approved Document L, Volume 2 — Buildings other than dwellings
Energy performance guidance for non-domestic buildings, covering fabric, services, controls and commissioning.
- Edition
- 2021 edition incorporating 2023 amendments · Volume 2; later editions and transitions on source page
- Search coverage
- 116 of 116 PDF pages · 2 OCR pages
Energy & sustainability
Open original PDF at page 52 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
L1(b), L2 O N L I N E V E R S I O N
Boiler controls
6.7 Boiler systems with an output of more than 100kW should have both of the following.
a. Optimum start/stop control with either:
i. night setback
ii. frost protection outside occupied periods.
b. Either:
i. two-stage high/low firing facility in boiler
ii. multiple boilers with sequence control to provide efficient part-load performance.
6.8 Gas-fired boilers and multi-stage oil-fired boilers with an output of more than 500kW should have
fully modulating burner controls.
Biomass boilers
6.9 The efficiency of biomass boilers at their nominal load and tested to BS EN 12809 should be no lower
than the following.
a. For independent gravity-fed boilers of ‹20.5kW output: 65%.
b. For independent automatic pellet/woodchip boilers: 75%.
Gas and oil-fired warm air heaters
6.10 In addition to meeting the general requirements for heating systems in Section 5, warm air systems
in new and existing buildings should meet the heat generator seasonal efficiency in Table 6.3.
Table 6.3 M inimum heat generator seasonal efficiency for gas and oil-fired warm air
heaters
Warm air heater type Heat generator seasonal efficiency Product standard
(net calorific value/thermal efficiency)
Gas-fired forced convection to 91% BS EN 621 for unfanned appliances
assist transportation of combustion BS EN 1020 for fanned appliances
air and/or combustion products
Direct gas-fired forced convection(1) n/a BS EN 525
Oil-fired forced convection 91% BS EN 13842
NOTE:
1. For direct gas-fired forced convection air heaters, 100% of the net heat input is delivered to the space. Specific
ventilation requirements as defined in BS EN 525 should be met.
Gas and oil-fired radiant heaters
6.11 In addition to meeting the general requirements for heating systems in Section 5, radiant heaters in
new and existing buildings should meet the heat generator seasonal efficiency in Table 6.4.
6.12 For flued appliances, thermal efficiency should be measured to either of the following test
standards, as applicable:
a. BS EN 1020
42
Approved Document L Volume 2, 2021 edition Building Regulations 2010
O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.