Regulation 43: Pressure testing
This section deals with the requirements of regulation 43 of the Building Regulations 2010.
Regulation
Pressure testing
43. (1) T his regulation applies to the erection of a building in relation to which paragraph L1(a)(i) of Schedule 1
imposes a requirement.
(2) W here this regulation applies, the person carrying out the work shall, for the purpose of ensuring compliance
with regulation 26 and regulation 26A and paragraph L1(a)(i) of Schedule 1—
(a) ensure that—
(i) p ressure testing is carried out in such circumstances as are approved by the Secretary of State; and
(ii) t he testing is carried out in accordance with a procedure approved by the Secretary of State; and
(b) s ubject to paragraph (5), give notice of the results of the testing to the local authority.
(3) T he notice referred to in paragraph (2)(b) shall—
(a) r ecord the results and the data upon which they are based in a manner approved by the Secretary of
State; and
(b) b e given to the local authority not later than seven days after the final test is carried out.
(4) A local authority are authorised to accept, as evidence that the requirements of paragraph (2)(a)(ii) have been
satisfied, a certificate to that effect by a person who is registered by Elmhurst Energy Systems Limited or
the Air Tightness Testing and Measurement Association in respect of pressure testing for the air tightness of
buildings.
(5) W here such a certificate contains the information required by paragraph (3)(a), paragraph (2)(b) does not
apply.
NOTE: Where the building control body is an approved inspector, see regulation 20 of the Building
(Approved Inspectors etc.) Regulations 2010 (as amended).
Intention
In the Secretary of State’s view, the requirements of regulation 43 are met, when a building is erected,
by carrying out pressure testing in accordance with paragraphs 7.2 to 7.5 and 7.9.
In the Secretary of State’s view, results from a pressure test must be used to show that work complies
with both of the following.
a. Regulation 26 and 26A of the Building Regulations, in accordance with paragraphs 7.6 to 7.8.
b. The requirements of Part L1(a)(i) of Schedule 1 to the Building Regulations, in accordance with
paragraphs 7.1 and 7.6.
56
Approved Document L Volume 2, 2021 edition Building Regulations 2010
O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.