Conservation of fuel and power: Approved Document L, Volume 2 — Buildings other than dwellings

Energy performance guidance for non-domestic buildings, covering fabric, services, controls and commissioning.

Energy & sustainability
Open original PDF at page 73

Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.

R44O, NRL I4N4E ZV EAR S,I OLN1(b), L2(b) Table 8.1 D uctwork pressure classes Ductwork pressure class Design static pressure (Pa) Maximum air Air leakage limit (l/(s·m2) velocity (m/s) of duct surface area)(1) Maximum positive Maximum negative Low pressure (class A) 500 500 10 0.027 ∆p0.65 Medium pressure (class B) 1000 750 20 0.009 ∆p0.65 High pressure (class C) 2000 750 40 0.003 ∆p0.65 High pressure (class D) 2000 750 40 0.001 ∆p0.65 NOTE: 1. ∆p is the differential pressure in pascals. 63 Building Regulations 2010 Approved Document L Volume 2, 2021 edition O N L I N E V E R S I O N