R44O, NRL I4N4E ZV EAR S,I OLN1(b), L2(b)
Table 8.1 D uctwork pressure classes
Ductwork pressure class Design static pressure (Pa) Maximum air Air leakage limit (l/(s·m2)
velocity (m/s) of duct surface area)(1)
Maximum positive Maximum negative
Low pressure (class A) 500 500 10 0.027 ∆p0.65
Medium pressure (class B) 1000 750 20 0.009 ∆p0.65
High pressure (class C) 2000 750 40 0.003 ∆p0.65
High pressure (class D) 2000 750 40 0.001 ∆p0.65
NOTE:
1. ∆p is the differential pressure in pascals.
63
Building Regulations 2010 Approved Document L Volume 2, 2021 edition