Conservation of fuel and power: Approved Document L, Volume 1 — Dwellings

Building regulation guidance on energy efficiency and the conservation of fuel and power.

Energy & sustainability
Open original PDF at page 95

Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.

O N L I N E V E R S I O N AD Table D1 Continued Hot water system Stored hot water in cylinder, heated by air source heat pump with back-up immersion heating Separate time control for space and water heating Wastewater heat recovery (WWHR) None Hot water cylinder If cylinder, declared loss factor = 0.85 ´ (0.2 + 0.051 V2/3) kWh/day where V is the volume of the cylinder in litres Lighting Fixed lighting capacity (lm) = 185 ´ total floor area Efficacy of all fixed lighting = 80 lm/W Air conditioning None Photovoltaic (PV) system None NOTES: 1. Changes from the notional dwelling specification (Table 1.1) are in bold. 2. See SAP 10 for details. 3. Space heating and water heating efficiencies as calculated in SAP 10; this is different from the COP. BBuuiillddiinngg RReegguullaattiioonnss 22001100 AApppprroovveedd DDooccuummeenntt LL VVoolluummee 11,, 22002211 eeddiittiioonn 8855 O N L I N E V E R S I O N

Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.