Protection from falling, collision and impact: Approved Document K

Guidance covering stairs, ladders, ramps, guarding and protection from collision and impact.

Stairs & circulation
Open original PDF at page 17

Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.

O N L I N E V E R S I O N K1 Stairs and ladders See paras 1.5–1.10 25mm max. 25mm max. overlap overlap 60° min. Diagram 1.2 Examples of suitable tread profiles Headroom for stairs For all buildings 1.11 On the access between levels, provide the minimum headroom shown in Diagram 1.3. See para 1.11 At least Minimum 2m headroom At least 2m At least Landing 2m Pitch line Flight Landing Diagram 1.3 Minimum headroom For buildings other than dwellings and for common access areas in buildings that contain flats 1.12 Provide all means of escape routes with a minimum clear headroom of 2m, except in doorways. Building Regulations 2010 AAAApppppppprrrroooovvvveeeedddd DDDDooooccccuuuument K, 2013 edition 7 OOO NNN LLL III NNN EEE VVV EEE RRR SSS III OOO NNN

Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.