England · Statutory guidance
Protection from falling, collision and impact: Approved Document K
Guidance covering stairs, ladders, ramps, guarding and protection from collision and impact.
- Edition
- 2013 edition; publisher updates on source page
- Search coverage
- 68 of 68 PDF pages · 1 OCR pages
Stairs & circulation
Open original PDF at page 18 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E V E R S I O N
K1
Stairs and ladders
See para 1.13
Where there is not enough space
to achieve 2m headroom reduced
headroom as shown will be
satisfactory
1.9m
1.8m
Half width of stair
Diagram 1.4 Reduced headroom for loft conversions
For loft conversions in dwellings
1.13 Where there is not enough space to achieve the height shown in Diagram 1.3, provide the reduced
headroom shown in Diagram 1.4.
Width of flights of stairs
For buildings other than dwellings
1.14 For stairs that form part of means of escape, refer also to Approved Document B: Fire safety,
Volume 2 – Buildings other than dwellinghouses.
1.15 For flights of stairs, provide all of the following.
a. A minimum stair width between enclosing walls, strings or upstands of 1200mm.
b. A minimum width between handrails of 1000mm.
c. If the flight is more than 2m wide, divide it into flights a minimum of 1000mm wide, as shown in
Diagram 1.5
d. For access for maintenance, see paragraph 1.42.
For dwellings
1.16 In exceptional circumstances where severely sloping plots are involved, a stepped change of level
within the entrance storey may be unavoidable. In those instances ensure that stairs within the
entrance storey of a dwelling have flights with a minimum stair width of 900mm.
8 Approved Documentttt KKKK,,,, 2222000011113333 eeeeddddiiiittttiiiioooonnnn Building Regulations 2010
OOO NNN LLL III NNN EEE VVV EEE RRR SSS III OOO NNN
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.