O N L I N E V E R S I O N K1 Stairs and ladders e. Use a surface for the handrail that is slip-resistant and which, in locations subject to extremely cold or hot temperatures, does not become excessively cold or hot to touch. In areas where resistance to vandalism or low maintenance are key factors, use of metals with relatively low thermal conductivity may be appropriate. f. Finish the end of the handrail in a way that reduces the risk of clothing being caught. g. Use the handrail profile shown in Diagram 1.13. See paras 1.34 and 1.36 900mm to 1000mm above pitch line 300mm min. 300mm min. 900mm to 1100mm 900mm to 1100mm Diagram 1.12 Key dimensions for handrails for stairs in buildings other than dwellings In dwellings 1.37 In exceptional circumstances where severely sloping plots are involved, a stepped change of level within the entrance storey may be unavoidable. In those instances, if a flight comprises three or more risers, provide a suitable continuous handrail in accordance with both of the following. a. On each side of the flight. b. On each side of any intermediate landings. Building Regulations 2010 AAAApppppppprrrroooovvvveeeedddd DDDDooooccccuuuument K, 2013 edition 15 OOO NNN LLL III NNN EEE VVV EEE RRR SSS III OOO NNN