K1
Stairs and ladders
e. Use a surface for the handrail that is slip-resistant and which, in locations subject to extremely
cold or hot temperatures, does not become excessively cold or hot to touch. In areas where
resistance to vandalism or low maintenance are key factors, use of metals with relatively low
thermal conductivity may be appropriate.
f. Finish the end of the handrail in a way that reduces the risk of clothing being caught.
g. Use the handrail profile shown in Diagram 1.13.
See paras 1.34 and 1.36
900mm to 1000mm above pitch line
300mm min.
300mm min. 900mm to 1100mm
900mm to 1100mm
Diagram 1.12 Key dimensions for handrails for stairs in buildings other than dwellings
In dwellings
1.37 In exceptional circumstances where severely sloping plots are involved, a stepped change of level
within the entrance storey may be unavoidable. In those instances, if a flight comprises three or
more risers, provide a suitable continuous handrail in accordance with both of the following.
a. On each side of the flight.
b. On each side of any intermediate landings.