K1
Stairs and ladders
See para 1.36 Circular handrail Non-circular handrail
32mm to 50mm 50mm wide and 39mm
diameter deep having rounded edges
50mm to
75mm
15mm min.
radius
50mm min.
50mm max.
Non-circular handrail
50 mm wide and
39 mm deep having
rounder edges
50mm min.
Ramped or
stepped
access
Diagram 1.13 Handrail design
Guarding of stairs
For all buildings
1.38 Design the guarding to be the height shown in Diagram 3.1.
1.39 In a building that may be used by children under five years of age, construct the guarding to a flight
of stairs to do both of the following.
a. Prevent children being held fast by the guarding: ensure that a 100mm sphere cannot pass
through any openings in the guarding.
b. Prevent children from readily being able to climb the guarding.