K1
Ramps
Section 2: Ramps
Scope
2.1 The guidance provided in this document covers internal and external ramps when they are part
of the building. Additional guidance is provided in Approved Document M when external ramped
access also forms part of the principal entrances and alternative accessible entrances, and when they
form part of the access route to the building from the boundary of the site and car parking. See
Approved Document M Section 1 (for buildings other than dwellings) and Section 6 (for dwellings).
Appearance of ramps
For buildings other than dwellings
2.2 Ensure that ramps are readily apparent or clearly signposted.
Steepness of ramps
For all buildings
2.3 Ensure that the relationship between the gradient of a ramp and its going between landings is as
shown in Diagram 2.1.
NOTE: A floor level with a gradient of 1:20 or steeper should be designed as a ramp.
See para 2.3
Diagram 2.1 Relationship of ramp gradient to the going of a flight
18 Approved Document K, 2013 edition Building Regulations 2010
pmar
fo
tneidarg
mumixaM
O N L I N E V E R S I O N
1:20 (500mm rise)
1:15 (333mm rise)
1:12 (166mm rise)
0 2 5 10
Going of ramp flight (m)
NOTE: For goings between 2m and 10m, it is acceptable to interpolate between the maximum gradients
i.e. 1:14 for 4m going or 1:19 for 9m going