England · Statutory guidance
Structure: Approved Document A
Guidance on structural loading, foundations, walls, floors, roofs and disproportionate collapse.
- Edition
- 2004 edition incorporating 2010 and 2013 amendments
- Search coverage
- 54 of 54 PDF pages · 1 OCR pages
Structure
Open original PDF at page 13 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E V E R S I O N
A1/2
Section 2A: Basic requirements for stability
2A1 This section must be used in conjunction
with sections 2B and 2C and its principles relate
to all forms of low-rise residential buildings.
2A2 Adequate provision shall be made to
ensure that the building is stable under the likely
imposed and wind loading conditions. This will
commonly necessitate meeting the following
requirements:
a. That the overall size and proportioning
of the building are limited in accordance
with the specific guidance for each form of
construction.
b. That a suitable layout of walls (both internal
and external) forming a robust 3 dimensional
box structure in plan is constructed with
restriction on the maximum size of cells
measured in accordance with the specific
guidance for each form of construction.
c. That the internal and external walls are
adequately connected either by masonry
bonding or by using mechanical connections.
d. That the intermediate floors and roof are of
such construction and interconnection with
the walls that they provide local support
to the walls and also act as horizontal
diaphragms capable of transferring the wind
forces to buttressing elements of the building.
Note: A traditional cut timber roof (i.e. using
rafters, purlins and ceiling joists) generally has
sufficient built in resistance to instability and wind
forces (e.g. from hipped ends, tiling battens, rigid
sarking or the like). However, the need for
diagonal rafter bracing equivalent to that
recommended in BS EN 1995-1-1:2004 with its
UK National Annex and additional guidance given
in BSI Published Document PD 6693-1:2012 and
BS 8103-3:2009 for trussed rafter roofs should
be considered, especially for single-hipped and
non-hipped roofs of greater than 40° pitch to
detached houses.
Approved Document A Structure
O N L I N E V E R S I O N 11
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.