England · Statutory guidance
Structure: Approved Document A
Guidance on structural loading, foundations, walls, floors, roofs and disproportionate collapse.
- Edition
- 2004 edition incorporating 2010 and 2013 amendments
- Search coverage
- 54 of 54 PDF pages · 1 OCR pages
Structure
Open original PDF at page 30 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E V E R S I O N
A1/2
THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS
Diagram 13 Buttressing
See para 2C27
2C29 Dimensional criteria for openings and Lateral support by roofs and floors
recesses:
2C32 A wall in each storey of a building should
The dimensional criteria are given in Diagram 14 extend to the full height of that storey, and have
and Table 8. horizontal lateral supports to restrict movement
No openings should be provided in walls below of the wall at right angles to its plane.
ground floor except for small holes for services
2C33 Floors and roofs should:
and ventilation, etc. which should be limited
to a maximum area of 0.1m² at not less than a. act to transfer lateral forces from walls to
2m centres. buttressing walls, piers or chimneys; and
2C30 Chases: b. be secured to the supported wall by
connections specified in paragraphs 2C34
a. vertical chases should not be deeper than 1/3 and 2C35.
of the wall thickness or, in cavity walls, 1/3 of
the thickness of the leaf; 2C34 The requirements for lateral restraint of
walls at roof and floor levels are given in Table 9
b. horizontal chases should not be deeper than and guidance on satisfying the requirements is
1/6 of the thickness of the leaf of the wall; given in paragraphs 2C35 and 2C36.
c. chases should not be so positioned as to 2C35 Walls should be strapped to floors above
impair the stability of the wall, particularly ground level, at intervals not exceeding 2m
where hollow blocks are used. and as shown in Diagram 15, by tension straps
conforming to BS EN 845-1. For corrosion
2C31 Overhangs:
resistance purposes, the tension straps should
The amount of any projection should not impair be material reference 14 or 16.1 or 16.2
the stability of the wall. (galvanised steel) or other more resistant
Continued on page 30
Structure Approved Document A
28 O N L I N E V E R S I O N