England · Statutory guidance
Structure: Approved Document A
Guidance on structural loading, foundations, walls, floors, roofs and disproportionate collapse.
- Edition
- 2004 edition incorporating 2010 and 2013 amendments
- Search coverage
- 54 of 54 PDF pages · 1 OCR pages
Structure
Open original PDF at page 31 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E V E R S I O N
A1/2
THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS
Diagram 14 Sizes of openings and recesses
See para 2C29
8 Take the value of the Factor X from Table 8, or it
can be given the value 6, provided the declared
compressive strength of the bricks or blocks (in the
case of a cavity wall – in the loaded leaf) is not less
than 7.3N/mm2.
Table 8 V alue of Factor ‘X’ (see Diagram 14)
Span of timber Span of concrete
floor into wall floor into wall
Span of floor
Minimum is parallel max max max max
Nature of Maximum thickness of to wall 4.5m 6.0m 4.5m 6.0m
roof span roof span (m) wall inner (mm)
Value of Factor ‘X’
Roof spans Not 100 6 6 6 6 6
parallel to wall applicable
90 6 6 6 6 5
Timber roof 9 100 6 6 5 4 3
spans into wall
90 6 4 4 3 3
Table 9 L ateral support for walls
Wall type Wall length Lateral support required
Solid or cavity: external Any length Roof lateral support by every roof forming a junction with the
compartment separating supported wall
Greater than 3m Floor lateral support by every floor forming a junction with the
supported wall
Internal load-bearing wall (not being Any length Roof or floor lateral support at the top of each storey
a compartment or separating wall)
Approved Document A Structure
O N L I N E V E R S I O N 29