England · Statutory guidance
Structure: Approved Document A
Guidance on structural loading, foundations, walls, floors, roofs and disproportionate collapse.
- Edition
- 2004 edition incorporating 2010 and 2013 amendments
- Search coverage
- 54 of 54 PDF pages · 1 OCR pages
Structure
Open original PDF at page 32 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
O N L I N E V E R S I O N
A1/2
THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS
Diagram 15 Lateral support by floors
See para 2C35
e. Restraint of internal walls
specifications including material references 1 or d. where floors are at or about the same level
3 (austenitic stainless steel). The declared tensile on each side of a supported wall, and
strength of tension straps should not be less contact between the floors and wall is either
than 8kN. continuous or at intervals not exceeding 2m.
Where contact is intermittent, the points of
Tension straps need not be provided:
contact should be in line or nearly in line on
a. in the longitudinal direction of joists in houses plan (see Diagram 15(e)).
of not more than 2 storeys, if the joists are
2C36 Gable walls should be strapped to roofs as
at not more than 1.2m centres and have at
shown in Diagram 16(a) and (b) by tension straps
least 90mm bearing on the supported walls
as described in 2C35.
or 75mm bearing on a timber wall-plate at
each end, and Vertical strapping at least 1m in length should be
provided at eaves level at intervals not exceeding
b. in the longitudinal direction of joists in houses
2m as shown in Diagram 16(c) and (d). Vertical
of not more than 2 storeys, if the joists
strapping may be omitted if the roof:
are carried on the supported wall by joist
hangers in accordance with BS EN 845-1 a. has a pitch of 15° or more, and
of the restraint type described by additional
b. is tiled or slated, and
guidance given in BSI Published Document
PD 6697:2010 and shown in Diagram 15(c), c. is of a type known by local experience to be
and are incorporated at not more than 2m resistant to wind gusts, and
centres, and
d. has main timber members spanning onto the
c. when a concrete floor has at least 90mm supported wall at not more than 1.2m centres.
bearing on the supported wall (see Diagram
15(d)), and
Structure Approved Document A
30 O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.