A1/2
THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS
Diagram 16 Lateral support at roof level
See para 2C36
Interruption of lateral support Small single-storey non-residential
2C37 Where an opening in a floor or roof for a buildings and annexes
stairway or the like adjoins a supported wall and
interrupts the continuity of lateral support, the 2C38 Size and proportion
following conditions should be satisfied for the
i. General
purposes of Section 2C:
The guidance given applies in the following
a. the maximum permitted length of the opening
circumstances:
is to be 3m, measured parallel to the supported
wall, and a. The floor area of the building or annexe does
not exceed 36m².
b. where a connection is provided by means
other than by anchor, this should be provided b. The walls are solidly constructed in brickwork
throughout the length of each portion of the or blockwork using materials which comply
wall situated on each side of the opening, and with paragraphs 2C19 to 2C22.
c. where a connection is provided by mild steel c. Where the floor area of the building or annexe
anchors, these should be spaced closer than exceeds 10m² the walls have a mass of not
2m on each side of the opening to provide less than 130kg/m².
the same number of anchors as if there were
Note: There is no surface mass limitation
no opening, and
recommended for floor areas of 10m² or less.
d. there should be no other interruption of
d. Access to the roof is only for the purposes of
lateral support.
maintenance and repair.
e. The only lateral loads are wind loads.
Approved Document A Structure
O N L I N E V E R S I O N 31