Structure: Approved Document A

Guidance on structural loading, foundations, walls, floors, roofs and disproportionate collapse.

Structure
Open original PDF at page 34

Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.

O N L I N E V E R S I O N A1/2 THICKNESS OF WALLS IN CERTAIN SMALL BUILDINGS Diagram 17 Size and location of openings See para 2C38 f. The maximum length or width of the building Published Document PD 6693-1:2012 or BS or annexe does not exceed 9m. 8103-3:2009. g. The height of the building or annexe does not i. Walls are tied to the roof structure vertically exceed the lower value derived from Diagram 2. and horizontally in accordance with paragraphs 2C32 to 2C36 and with horizontal lateral h. The roof is braced at rafter level, horizontally restraint at roof level in accordance with at eaves level and at the base of any gable by paragraph (iv) below. roof decking, rigid sarking or diagonal timber bracing, as appropriate, in accordance with j. The roof structure of an annexe is secured BS EN 1995-1-1:2004 with its UK National to the structure of the main building at both Annex and additional guidance given in BSI rafter and eaves level. Structure Approved Document A 32 O N L I N E V E R S I O N