Structure: Approved Document A

Guidance on structural loading, foundations, walls, floors, roofs and disproportionate collapse.

Structure
Open original PDF at page 37

Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.

O N L I N E V E R S I O N A1/2 Section 2D: Proportions for masonry chimneys above the roof surface Height to width relationship 2D1 Where a chimney is not adequately supported by ties or securely restrained in any way, its height if measured from the highest point of intersection with the roof surface, gutter, etc. should not exceed 4.5W, provided the density of the masonry is greater than 1500kg/m3, where: W is the least horizontal dimension of the chimney measured at the same point of intersection, and H is measured to the top of any chimney pot or other flue terminal (see Diagram 20). Diagram 20 Proportions for masonry chimneys See para 2D1 Approved Document A Structure O N L I N E V E R S I O N 35