England · Statutory guidance
Ventilation: Approved Document F, Volume 1 — Dwellings
Building regulation guidance on ventilation for dwellings and other buildings.
- Edition
- 2021 edition · Volume 1; later editions and transitions on source page
- Search coverage
- 62 of 62 PDF pages · 2 OCR pages
Ventilation
Open original PDF at page 28 Source wording and page order preserved. Drawings and table layouts remain available in the original PDF.
F1(1) O N L I N E V E R S I O N
Control of ventilation intakes
2.2 Ventilation intakes should be located away from the direct impact of the sources of local pollution.
NOTE: CIBSE’s TM64 and TM40 give further guidance.
2.3 Where urban traffic is a source of pollution, the air intakes for dwellings next to busy urban roads
should be both of the following.
a. As high as possible.
b. Located on the less polluted side of the building.
Mechanical ventilation may be the most practical way of achieving this requirement.
2.4 If practicable, ventilation intakes should not be located in courtyards or enclosed urban spaces
where air pollutants are discharged. If this is unavoidable, intakes should be located to meet both
of the following conditions.
a. As far as possible from the source of pollutants.
b. In an open or well-ventilated area.
2.5 In areas where wind often comes from opposing directions (e.g. a valley), the air intakes should
point in the opposite direction to the exhaust outlets.
2.6 Where sources of pollution vary with the time of day, such as urban road traffic, it may be
acceptable, for time-limited periods, to take one of the following actions.
a. Reduce the flow of external air into ventilation intakes.
b. Close ventilation intakes when the concentrations of external pollutants are highest.
NOTE: In these circumstances, expert advice should be sought.
Location of exhaust outlets
2.7 Exhaust outlets should be located so that both of the following are achieved.
a. Re-entry of exhaust air into a building, or entry into nearby buildings, is minimised.
b. There is no harmful effect on the surrounding area.
2.8 Where there is a prevailing wind direction, exhaust outlets should be downwind of intakes.
2.9 Exhaust outlets should not discharge into any of the following.
a. Courtyards.
b. Enclosures.
c. Architectural screens.
NOTE: Chapter 13 of McGraw Hill’s Indoor Air Quality Handbook provides further guidance.
20
Approved Document F Volume 1, 2021 edition Building Regulations 2010
O N L I N E V E R S I O N
Edition and local adoption determine which requirements apply. Use the publisher’s document for the complete clauses, diagrams and amendments.