TECHNICAL CHAPTER 3: BUILDING BLOCKS
308.2 Forward Reach.
308.2.1 Unobstructed. Where a forward reach is unobstructed, the high forward reach shall be 48
inches (1220 mm) maximum and the low forward reach shall be 15 inches (380 mm) minimum above
the finish floor or ground.
Figure 308.2.1
Unobstructed Forward Reach
308.2.2 Obstructed High Reach. Where a high forward reach is over an obstruction, the clear floor
space shall extend beneath the element for a distance not less than the required reach depth over
the obstruction. The high forward reach shall be 48 inches (1220 mm) maximum where the reach
depth is 20 inches (510 mm) maximum. Where the reach depth exceeds 20 inches (510 mm), the
high forward reach shall be 44 inches (1120 mm) maximum and the reach depth shall be 25 inches
(635 mm) maximum.
Figure 308.2.2
Obstructed High Forward Reach
308.3 Side Reach.
308.3.1 Unobstructed. Where a clear floor or ground space allows a parallel approach to an
element and the side reach is unobstructed, the high side reach shall be 48 inches (1220 mm)
114 - 2010 Standards: Titles II and III Department of Jus1ti5c1e
Titles II and III - 2010 Standards - 85