Analysis and Com menta ry on the 201 0 A DAStandards
able to satisfy the requirement to provide Visible Alarms. Section 215.3 of the 2010
accessible circulation paths by ensuring that Standards provides that where employee
their required primary circulation paths are work areas in newly constructed facilities
accessible. have audible alarm coverage they are
required to have wiring systems that
Individual employee work stations, such as a are capable of supporting visible alarms
grocery checkout counter or an automobile that comply with section 702 of the 2010
service bay designed for use by one person, Standards. The 1991 Standards, at section
do not contain common use circulation paths 4.1.1(3), require visible alarms to be provided
and are not required to comply. Other work where audible fire alarm systems are
areas, such as stockrooms that typically have provided, but do not require areas used only
narrow pathways between shelves, would by employees as work areas to be equipped
be required to design only one accessible with accessibility features. As applied to office
circulation path into the stockroom. It would buildings, the 1991 Standards require visible
not be necessary to make each circulation alarms to be provided in public and common
path in the room accessible. In alterations use areas such as hallways, conference
it may be technically infeasible to provide rooms, break rooms, and restrooms, where
accessible common use circulation paths in audible fire alarm systems are provided.
some employee work areas. For example,
in a stock room of a department store Commenters asserted that the requirements
significant existing physical constraints, such of section 215.3 of the 2010 Standards would
as having to move walls to avoid the loss of be burdensome to meet. These commenters
space to store inventory, may mean that it also raised concerns that all employee work
is technically infeasible (see section 106.5 areas within existing buildings and facilities
“Defined Terms” of the 2010 Standards) must be equipped with accessibility features.
to make even the primary common use
circulation path in that stock room wide The commenters’ concerns about section
enough to be accessible. In addition, the 215.3 of the 2010 Standards represent
2010 Standards include exceptions for a misunderstanding of the requirements
common use circulation paths in employee applicable to employee work areas.
work areas where it may be difficult to Newly constructed buildings and facilities
comply with the technical requirements for merely are required to provide wiring so
accessible routes due to the size or function that visible alarm systems can be added as
of the areas. The Department believes that needed to accommodate employees who
these exceptions will provide the flexibility are deaf or hard of hearing. This is a minimal
necessary to ensure that this requirement requirement without significant impact.
does not interfere with legitimate business
operations.